Three-phase transformers auto refrigerated
KVA | Average noise level (dB) | Average noise level (dB) |
Open | Encapsulated | |
0-9 | 40 | 45 |
10-50 | 45 | 50 |
51-150 | 50 | 55 |
151-300 | 55 | 57 |
301-500 | 60 | 59 |
501-700 | 62 | 61 |
701-1 000 | 64 | 63 |
1 001-1 500 | 65 | 64 |
1 501-2 000 | 66 | 65 |
2 001-3 000 | 68 | 66 |
3 001-4 000 | 70 | 68 |
4 001-5 000 | 71 | 69 |
5 001-6 000 | 72 | 70 |
6 001-7 500 | 75 | 71 |
7 501-10 000 | 79 | 72 |
Open three-phase transformers refrigerated forced air
KVA | Average noise level (dB) |
0-1167 | 67 |
1 168-1 667 | 68 |
1 668-2 000 | 69 |
2 001-3 333 | 71 |
3 334-5 000 | 73 |
5 001-6 667 | 73 |
6 668- 8 333 | 75 |
8 334-10 000 | 78 |
Single-phase transformers self- refrigerated
KVA | Nivel de ruido promedio (dB) | Nivel de ruido promedio (dB) |
Abiertos | Encapsulados | |
0-50 | 50 | 50 |
51-167 | 55 | 55 |
168-333 | 60 | 60 |
500 | 64 | 63 |
833 | 65 | 64 |
1 256 | 68 | 66 |
1 667 | 70 | 68 |
2 500 | 71 | 70 |
3 333 | 72 | 71 |
5 000 | 73 | 72 |
10 000 | 79 | 72 |
KVA | Nivel de ruido promedio (dB) |
0-50 | 67 |
51-167 | 67 |
168-333 | 67 |
500 | 67 |
833 | 68 |
1 256 | 70 |
1 667 | 71 |
2 500 | 72 |
3 333 | 74 |
5 000 | 76 |
10 000 | 78 |
The data included in the tables are based on the Colombian technical standard NTC 5978.